To meet safety and electromagnetic interference (EMI) requirements and to ensure
proper operation, you must connect the QFX3500 device to earth ground before you
connect it to power.
For installations that require a separate grounding conductor to the chassis, you must
attach a protective earthing terminal bracket on the QFX3500 device left front mounting
bracket to connect to the earth ground (see
Figure 52 on page 217
).
Before you connect earth ground to the protective earthing terminal of a QFX3500 device,
ensure that a licensed electrician has attached an appropriate grounding lug to the
grounding cable.
CAUTION:
Using a grounding cable with an incorrectly attached lug can
damage the device.
NOTE:
Mount your device in the rack or cabinet before attaching the grounding
lug to the device. See
“Mounting a QFX3500 Device in a Rack or Cabinet” on
page 213
.
Ensure that you have the following parts and tools available:
•
Protective earthing terminal bracket—This L-shaped bracket attaches to a post on the
QFX3500 device left front mounting bracket, providing a protective earthing terminal
for the device. This bracket is provided in the accessory kit.
•
Grounding cable for your QFX3500 device—The grounding cable must be 14 AWG
(2 mm²), minimum 90° C wire, or as permitted by the local code.
•
Grounding lug for your grounding cable—The grounding lug required is a Panduit
LCD10-10A-L or equivalent. This grounding lug is provided in the accessory kit.
•
Three M4 hex nuts with integrated washers—One nut and washer are required to secure
the grounding lug bracket to the left front mounting bracket, and two nuts and washers
are used to secure the grounding lug to the grounding lug bracket protective earthing
terminal. Four nuts are provided in the accessory kit.
•
7-mm wrench or socket with driver to attach all three nuts.
An AC-powered QFX3500 device chassis gains additional grounding when you plug the
power supply in the device into a grounded AC power outlet by using an AC power cord
appropriate for your geographical location. See
“AC Power Cord Specifications for a
QFX3500, QFX3600, or QFX3600-I Device” on page 139
.
To connect earth ground to a QFX3500 device:
Copyright © 2015, Juniper Networks, Inc.
216
QFX3000-G QFabric System Deployment Guide
Summary of Contents for QFX3000-G QFabric
Page 12: ...Copyright 2015 Juniper Networks Inc xii QFX3000 G QFabric System Deployment Guide...
Page 28: ...Copyright 2015 Juniper Networks Inc 2 QFX3000 G QFabric System Deployment Guide...
Page 102: ...Copyright 2015 Juniper Networks Inc 76 QFX3000 G QFabric System Deployment Guide...
Page 108: ...Copyright 2015 Juniper Networks Inc 82 QFX3000 G QFabric System Deployment Guide...
Page 154: ...Copyright 2015 Juniper Networks Inc 128 QFX3000 G QFabric System Deployment Guide...
Page 168: ...Copyright 2015 Juniper Networks Inc 142 QFX3000 G QFabric System Deployment Guide...
Page 180: ...Copyright 2015 Juniper Networks Inc 154 QFX3000 G QFabric System Deployment Guide...
Page 270: ...Copyright 2015 Juniper Networks Inc 244 QFX3000 G QFabric System Deployment Guide...
Page 294: ...Copyright 2015 Juniper Networks Inc 268 QFX3000 G QFabric System Deployment Guide...
Page 300: ...Copyright 2015 Juniper Networks Inc 274 QFX3000 G QFabric System Deployment Guide...
Page 394: ...Copyright 2015 Juniper Networks Inc 368 QFX3000 G QFabric System Deployment Guide...
Page 468: ...Copyright 2015 Juniper Networks Inc 442 QFX3000 G QFabric System Deployment Guide...
Page 470: ...Copyright 2015 Juniper Networks Inc 444 QFX3000 G QFabric System Deployment Guide...
Page 608: ...Copyright 2015 Juniper Networks Inc 582 QFX3000 G QFabric System Deployment Guide...
Page 640: ...Copyright 2015 Juniper Networks Inc 614 QFX3000 G QFabric System Deployment Guide...