Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-78-
2. Logic diagram for restart after power off
Standby
Running state
before power off
0
1
P01.21
Restart at power off
Wait time of restart
at power off > P01.22
0
1
2
Stop
Run
0
1
P01.18
Power-on terminal running protection
selection
Delay time of restart
> P01.23
N
Y
Y
N
Restart after
power off
Run
Stop
Whether FWD/REV running
terminal command is valid
N
Run
Y
P00.01
Running command channel
Keypad
Communi
cation
Terminal
3. Logic diagram for restart after automatic fault reset
VFD fault
In running
Auto VFD fault reset
count < P08.28
Auto VFD fault reset
interval > P08.29
Start running after
VFD fault reset
Display the fault
code and stop
N
N
Y
Y
Related parameter list:
Function
code
Name
Description
Default
P00.01
Channel of running commands
0: Keypad
1: Terminal
2: Communication
0
P00.11
ACC time 1
0.0
–3600.0s
Model
depended
P00.12
DEC time 1
0.0
–3600.0s
Model
depended
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Speed tracking restart 1
3: Speed tracking restart 2
0
P01.01
Starting frequency of direct
start
0.00
–50.00Hz
0.50Hz
P01.02
Starting frequency hold time
0.0
–50.0s
0.0s
P01.03
Braking current before start
0.0
–100.0%
0.0%
P01.04
DC braking time before start
0.00
–50.00s
0.00s
P01.05
ACC and DEC mode
0: Linear
0