Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-108-
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Keypad
AI1
CANopen
Modbus
PID
Multi-step speed
Simple PLC
Reserved
AI3
AI2
Ethernet
P00.06
(A frequency command selection)
Frequency set
through keypad
P00.10
P08.05
Amplitude of wobbling frequency
*
*
Keep present
frequency
Set frequency
P00.11 (ACC time 1)
P00.12 (DEC time 1)
Wobbling
frequency
output
Terminal function 26
(Pause wobbling
frequency)
Terminal function 27
(Reset wobbling
frequency)
Valid
Invalid
Valid
Invalid
Reserved
EtherCAT/PROFINET
PLC card
Pulse string AB
PROFIBUS/DeviceNet
Function
code
Name
Description
Default
P00.03
Max. output frequency
P00.03
–400.00Hz
50.00Hz
P00.06
Setting channel of A frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: Reserved
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus communication
9: CANopen communication
10: Ethernet communication
11: Reserved
12: Pulse train AB
13: EtherCAT/PROFINET communication
14: Programmable expansion card
15: PROFIBUS-DP/DeviceNet
communication
0
P00.11
ACC time 1
0.0
–3600.0s
Model
depended
P00.12
DEC time 1
0.0
–3600.0s
Model
depended
P05.01
–
P05.04
Digital input function selection
26: Pause wobbling frequency (stopped at
the present frequency)
27: Reset wobbling frequency (returned to
the center frequency)
/
P08.15
Amplitude of wobbling
frequency
0.0
–100.0% (relative to set frequency)
0.0%
P08.16
Amplitude of sudden jump
frequency
0.0
–50.0% (relative to amplitude of wobbling
frequency)
0.0%
P08.17
Rise time of wobbling
frequency
0.1
–3600.0s
5.0s
P08.18
Fall time of wobbling frequency 0.1
–3600.0s
5.0s