Goodrive600 series high-performance multifunction VFD
Function parameter list
-241-
Function
code
Name
Description
Default Modify
0: Communication password protection is invalid.
1: Communication password protection is valid.
P21 group
––CANopen communication
Function
code
Name
Description
Default Modify
P21.00
Reserved
P21.01
CANopen
communication address
0
–127
1
○
P21.02
–
P21.12
Reserved
P21.13
Sent PZD2
Used when the rectifier unit works as the
CANopen slave node or used in
PLC-to-CANopen networking.
0: Invalid
1: Fault code
2: DC voltage (* 10, V)
3: Grid voltage (* 1, V)
4: Grid frequency (* 10, Hz)
5: Brake current (* 10, A)
6: Terminal input status
7: Terminal output status
8: Number of online slave nodes
9: Online/offline state of slave nodes 02
–17
10: Online/offline state of slave nodes 18
–21
11: CANopen bus load rate
12: Type of card at slot 1
13: Type of card at slot 2
14: Software version of card at slot 1
15: Software version of card at slot 2
16: R-phase current
17: S-phase current
18: T-phase current
19: Node number of first CANopen offline unit
20: Reserved
0
○
P21.14
Sent PZD3
0
○
P21.15
Sent PZD4
0
○
P21.16
Sent PZD5
0
○
P21.17
Sent PZD6
0
○
P21.18
Sent PZD7
0
○
P21.19
Sent PZD8
0
○
P21.20
Sent PZD9
0
○
P21.21
Sent PZD10
0
○
P21.22
Sent PZD11
0
○
P21.23
Sent PZD12
0
○
P21.24
–
P21.28
Reserved
P21.29
CANopen
communication baud
rate
Setting range: 0
–5
0: 50Kbps
1: 100 Kbps
2: 125Kbps
3: 250Kbps
4: 500Kbps
5: 1M bps
3
○
P21.30
CANopen
communication
timeout time
0.0 (invalid); 0.1
–100.0s
0.0s
○