Goodrive600 series high-performance multifunction VFD
Technical data
-392-
IEC/EN 62061
Safety of machinery
––Safety-related functional safety of electrical, electronic, and
programmable electronic control systems
IEC/EN 61800-3
Adjustable speed electrical power drive systems
––Part 3:EMC requirements and
specific test methods
IEC/EN 61800-5-1
Adjustable speed electrical power drive systems
––Part 5-1: Safety
requirements
—Electrical, thermal and energy
IEC/EN 61800-5-2
Adjustable speed electrical power drive systems
––Part 5-2: Safety requirements––
Function
C.5.1 CE marking
The CE marking on the VFD nameplate indicates that the VFD is CE-compliant, meeting the regulations of the European
low-voltage directive (2014/35/EU) and EMC directive (2014/30/EU).
C.5.2 EMC compliance declaration
European union (EU) stipulates that the electric and electrical devices sold in Europe cannot generate electromagnetic
disturbance that exceeds the limits stipulated in related standards, and can work properly in environments with certain
electromagnetic interference. The EMC product standard (EN 61800-3) describes the EMC standards and specific test
methods for adjustable speed electrical power drive systems. Our products have been compliant with these EMC
regulations.
C.6 EMC regulations
The EMC product standard (EN 61800-3) describes the EMC requirements on VFDs.
Application environment categories:
First environment: Civilian environments, including application scenarios where VFDs are directly connected to the civil
power supply low-voltage grids without intermediate transformers
Second environment: All environments except those in Category I.
VFD categories:
C1: Rated voltage lower than 1000 V, applied to environments of Category I.
C2: Rated voltage lower than 1000 V, non-plug, socket, or mobile devices; power drive systems that must be installed
and operated by specialized personnel when applied to environments of Category I
Note: The EMC standard IEC/EN 61800-3 no longer restricts the power distribution of VFDs, but it specifies their
use, installation, and commissioning. Specialized personnel or organizations must have the necessary skills
(including the EMC-related knowledge) for installing and/or performing commissioning on the electrical drive
systems.
C3: Rated voltage lower than 1000 V, applied to environments of Category II. They cannot be applied to environments of
Category I.
C4: Rated voltage higher than 1000 V, or rated current higher or equal to 400 A, applied to complex systems in
environments of Category II.
C.6.1 VFD category C2
The induction disturbance limit meets the following stipulations:
1. Select an optional EMC filter according to Appendix E Optional peripheral accessories and install it following the
description in the EMC filter manual.