Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-97-
The following table lists the options of function parameters P06.01
–P06.04. A same output terminal function can be
repeatedly selected.
Setting
Function
Description
0
Invalid
The output terminal does not have any function.
1
Running
When the inverter unit works properly and there is frequency
output, it outputs the ON signal.
2
Running forward
When the inverter runs forward and there is frequency output,
it outputs the ON signal.
3
Running reversely
When the inverter unit runs reversely and there is frequency
output, it outputs the ON signal.
4
Jogging
When the inverter unit jogs and there is frequency output, it
outputs the ON signal.
5
Inverter unit fault
When the inverter unit encounters a fault, it outputs the ON
signal.
6
Frequency level detection FDT1 Refer to the descriptions for P08.32
–P08.33.
7
Frequency level detection FDT2 Refer to the descriptions for P08.34
–P08.35.
8
Frequency reached
Refer to the description for P08.36.
9
Running in zero speed
When both the inverter unit output frequency and reference
frequency are zero, it outputs the ON signal.
10
Upper limit frequency reached
When the running frequency of the inverter unit reaches the
upper limit, it outputs the ON signal.
11
Lower limit frequency reached
When the running frequency of the inverter unit reaches the
lower limit, it outputs the ON signal.
12
Ready for running
When the main circuit and control circuit powers are
established, the inverter unit protection functions do not act,
and the inverter unit is ready to run, it outputs the ON signal.
13
Pre-exciting
When the inverter unit is pre-exciting, it outputs the ON
signal.
14
Overload pre-alarm
When the pre-alarm time elapsed if the inverter unit
pre-alarm threshold is reached, it outputs the ON signal. For
details, see the descriptions for P11.08
–P11.10.
15
Underload pre-alarm
When the pre-alarm time elapsed if the inverter unit
pre-alarm threshold is reached, it outputs the ON signal. For
details, see the descriptions for P11.11
–P11.12.
16
Simple PLC stage completed
When the present state of the simple PLC is completed, it
outputs a signal.
17
Simple PLC cycle completed
When a single cycle of the simple PLC is completed, it outpus
a signal.
23
Modbus communication virtual
terminal output
A signal is output based on the value set through Modbus
communication. When the value is 1, the ON signal is output;
when the value is 0, the OFF signal is output.
24
POROFIBUS/DeviceNet
communication virtual terminal
output
A signal is output based on the value set through
POROFIBUS/DeviceNet communication. When the value is
1, the ON signal is output; when the value is 0, the OFF
signal is output.
25
Ethernet communication virtual
terminal output
A signal is output based on the value set through Ethernet
communication. When the value is 1, the ON signal is output;
when the value is 0, the OFF signal is output.
26
DC bus voltage established
When the bus voltage is above the inverter undervoltage, the