Goodrive600 series high-performance multifunction VFD
Communication networking
-202-
When an IN/OUT module selects 8 words or less, the mapping starts from CW/SW and it supports data reading and
writing of up to 3 PZDs (PZD2
–PZD4), but it does not support reading and writing of function codes.
6.6.6 Related parameters
Table 6-41 Rectifier unit related parameters
Function
code
Name
Description
Default
Modify
P00.01
Channel of running
commands
Used to select the channel of rectifier unit control
commands,
including the start, stop, and fault reset
commands.
0: Keypad
The running commands are controlled through
keypad keys, such as RUN and STOP/RST.
1: Terminal
The running commands such as run, stop, and
fault reset are controlled through multi-function
input terminals.
2: Communication
The running commands are controlled by the
upper computer in communication mode.
1
○
P00.02
Communication mode
of running commands
Used to select the rectifier unit communication
command mode.
0: RS485
1: CANopen
2: PLC
3: PROFIBUS-DP
4: PROFINET/EtherCAT
0
○
P17.15
Actual online slave
nodes
Number of actual online slave nodes.
Range: 0
–20
0
●
P17.16
Type of card at slot 1 Used to display the type of card at the slot.
Range: 0
–18
0: No card
1: PLC
2: I/O
3
–4: Reserved
5: Ethernet
6: PROFIBUS-DP
7: Reserved
8: Reserved
9: Reserved
10: Reserved
11
–14: Reserved
15: PROFINET
16: Modbus
17: EtherCAT
18: BACnet
0
●
P17.17
Type of card at slot 2
0
●
P17.18
Software version of
card at slot 1
Used to display the software version of the card
at slot 1.
0.00
●