Goodrive600 series high-performance multifunction VFD
Function parameter list
-301-
Function
code
Name
Description
Default Modify
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note: The baud rate of the upper computer
must be the same as the inverter unit;
otherwise, communication cannot be
performed. A greater baud rate indicates
faster communication.
P14.02
Data bit check
The data format of the upper computer must be
the same as the inverter unit; otherwise,
communication cannot be performed.
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
1
○
P14.03
Communication
response delay
0
–200ms
Used to indicate the communication response
delay, that is, the interval from when the inverter
unit completes receiving data to when it sends
response data to the upper computer. If the
response delay is shorter than the rectifier
processing time, the rectifier sends response
data to the upper computer after processing
data. If the delay is longer than the rectifier
processing time, the rectifier does not send
response data to the upper computer until the
delay is reached although data has been
processed.
5
○
P14.04
Communication timeout
time
0.0 (invalid)
–60.0s
When the function code is set to 0.0, the
communication timeout time is invalid.
When the function code is set to a non-zero
value, the system reports the "485
communication fault" (CE) if the communication
interval exceeds the value.
In general, the function code is set to 0.0. When
continuous communication is required, you can
set the function code to monitor communication
status.
0.0s
○
P14.05
Transmission error
processing
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
0
○