Goodrive600 series high-performance multifunction VFD
Function parameter list
-293-
Function
code
Name
Description
Default Modify
BIT7
BIT6 11 00
01
10
11
BIT9
BIT8 12 00
01
10
11
BIT11 BIT10 13 00
01
10
11
BIT13 BIT12 14 00
01
10
11
BIT15 BIT14 15 00
01
10
11
Select corresponding acceleration/deceleration
time, and then convert 16-bit binary number into
hexadecimal number, finally, and then set
corresponding function codes.
ACC/DEC time 1 is set by P00.11 and P00.12;
ACC/DEC time 2 is set by P08.00 and P08.01;
ACC/DEC time 3 is set by P08.02 and P08.03;
ACC/DEC time 4 is set by P08.04 and P08.05.
Setting range: 0x0000
–0xFFFF
P10.36
PLC restart mode
0: Restart from the first step, namely if the VFD
stops during running (caused by stop command,
fault or power down), it will run from the first step
after restart.
1: Continue running from the step frequency
when interruption occurred, namely if the VFD
stops during running (caused by stop command
or fault), it will record the running time of current
step, and enters this step automatically after
restart, then continue running at the frequency
defined by this step in the remaining time.
0
◎
P10.37
Multi-step time unit
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
0
◎
P11 group
––Protection parameters
Function
code
Name
Description
Default Modify
P11.00
Phase-loss protection
0x000
–0x010
Ones place: Reserved
Tens place: Output phase loss protection
selection
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place: Reserved
0x010
○
P11.01
Frequency drop at
transient power-off
0: Disable
1: Enable
0
○
P11.02
Reserved
0
–65535
0
○
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
1
○