Goodrive600 series high-performance multifunction VFD
Function parameter list
-278-
Function
code
Name
Description
Default Modify
Bit 12: Set torque (% on)
Bit 13: Count value
Bit 14: Motor overload percentage (% on)
Bit 15: PLC and current step number of
multi-step speed
P07.06
Selection 2 of
parameters to be
displayed in the running
state
0x0000
–0xFFFF
Bit 0: AI1 (V on)
Bit 1: AI1 (V on)
Bit 2: AI3 (V on)
Bit 3: Reserved
Bit 4: Reserved
Bit 5: Inverter overload percentage (% on)
Bit 6: Ramp frequency reference (Hz on)
Bit 7: Linear speed
Bit 8: AC incoming current
Bit 9
–15: Reserved
0x0000
P07.07
Selection of parameters
to be displayed in the
stop state
0x0000
–0xFFFF
BIT0: Set frequency (Hz on, blinking slowly)
Bit 1: Bus voltage (V on)
Bit 2: Input terminal state
Bit 3: Output terminal state
Bit 4: PID reference value (% blinking)
Bit 5: PID feedback value (% on)
Bit 6: Set torque (% on)
Bit 7: AI1 (V on)
Bit 8: AI2 (V on)
Bit 9: AI3 (V on)
Bit 10: Reserved
Bit 11: Reserved
Bit 12: Count value
Bit 13: PLC and current step number of
multi-step speed
Bit 14
–15: Reserved
0x00FF
○
P07.08
Frequency display
coefficient
0.01
–10.00
Display frequency = Running frequency * P07.08
1.00
○
P07.09
Rotational speed
display coefficient
0.1
–999.9%
Mechanical rotation speed = 120 * (Displayed
running frequency) * P07.09/(Motor pole pairs)
100.0%
○
P07.10
Linear speed display
coefficient
0.1
–999.9%
Linear speed=(Mechanical rotation speed) *
1.0%
○
P07.11
Heat sink temperature -20.0
–120.0°C
/
●
P07.12
Inverter temperature
-20.0
–120.0°C
/
●
P07.13
Control board software
version
1.00
–655.35
/
●
P07.14
Local accumulative
running time
0
–65535h
/
●
P07.15
Inverter unit electricity Used to display the electricity consumption of the
/
●