Goodrive600 series high-performance multifunction VFD
Communication networking
-174-
Table 6-27 Inverter unit related parameters
Function
code
Name
Description
Default
Modify
P00.01
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
○
P00.02
Communication mode
of running commands
0: Modbus
1: CANopen
2: Ethernet
3: EtherCAT/PROFINET
4: PLC
5: Wireless communication
6: PROFIBUS-DP/DeviceNet
Note: The options 2, 3, 4, 5, and 6 are
add-on functions and are available only
when corresponding expansion cards
are configured.
0
○
P00.06
Setting channel of A
frequency command
0: Keypad
1: AI1
2: AI2
3: AI3
4: Reserved
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus communication
9: CANopen communication
10: Ethernet communication
11: Reserved
12: Pulse train AB
13: EtherCAT/PROFINET communication
14: Programmable expansion card
15: PROFIBUS-DP/DeviceNet
communication
0
○
P07.27
Type of present fault 0: No fault
1: Inverter unit U-phase protection (OUt1)
2: Inverter unit V-phase protection (OUt2)
3: Inverter unit W-phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed
running (OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed
running (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: Inverter unit overload (OL2)
/
●
P07.28
Last fault type
/
●
P07.29
2nd-last fault type
/
●
P07.30
3rd-last fault type
/
●
P07.31
4th-last fault type
/
●
P07.32
5th-last fault type
/
●