Goodrive600 series high-performance multifunction VFD
Function parameter list
-270-
Function
code
Name
Description
Default Modify
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Hold
Forward
running
Reverse
running
1: Two-wire control 2, the enabling separated
from the direction. In this mode, FWD is the
enabling terminal. The direction depends on the
defined REV state.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Stop
Forward
running
Reverse
running
2: Three-wire control 1. This mode defines Sin as
the enabling terminal, and the running command
is generated by FWD, while the direction is
controlled by REV. During inverter unit running,
the Sin terminal needs to be closed. The terminal
FWD generates a rising edge signal, and then
the inverter unit starts to run in the direction set
by the state of terminal REV; the inverter unit
needs to be stopped by disconnecting terminal
Sin.
COM
K
SB2
SB1
FWD
REV
SIn
The direction control is as follows during running:
Sin
REV
Previous
direction
Present
direction
ON
OFF→ON
FWD run REV run
REV run FWD run
ON
ON→OFF
REV run FWD run
FWD run REV run
ON→OFF
ON
Decelerate to stop
OFF