Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-80-
Function
code
Name
Description
Default
braking for stop
P01.32
Pre-exciting time for jogging
0
–10.000s
0.000s
P01.33
Starting frequency of braking
for stop in jogging
0
–P00.03
0.00Hz
P01.34
Sleep delay
0
–3600.0s
0.0s
P05.01
–
P05.04
Digital input function selection
1: Run forward
2: Run reversely
4: Jog forward
5: Jog reversely
6: Coast to stop
7: Reset faults
8: Pause running
21: ACC/DEC time selection 1
22: ACC/DEC time selection 2
30: Disable ACC/DEC
/
P08.00
ACC time 2
0.0
–3600.0s
Model
depended
P08.01
DEC time 2
0.0
–3600.0s
Model
depended
P08.02
ACC time 3
0.0
–3600.0s
Model
depended
P08.03
DEC time 3
0.0
–3600.0s
Model
depended
P08.04
ACC time 4
0.0
–3600.0s
Model
depended
P08.05
DEC time 4
0.0
–3600.0s
Model
depended
P08.06
Running frequency of jog
0.00Hz
–P00.03 (Max. output frequency)
5.00Hz
P08.07
ACC time for jogging
0.0
–3600.0s
Model
depended
P08.08
DEC time for jogging
0.0
–3600.0s
Model
depended
P08.19
Switching frequency of
ACC/DEC time
0.00
–P00.03 (Max. frequency)
0.00Hz: No switchover
If the running frequency is greater than
P08.19, switch to ACC/DEC time 2.
0
P08.21
Reference frequency of
ACC/DEC time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid only for straight-line ACC/DEC
0
P08.28
Auto fault reset count
0
–10
0
P08.29
Auto fault reset interval
0.1
–3600.0s
1.0s
5.6.8 Frequency setting
The inverter unit supports multiple types of frequency reference modes, which can be categorized into: main reference
channel and auxiliary reference channel.
There are two main reference channels, namely frequency reference channel A and frequency reference channel B.
These two channels support simple arithmetical operation between each other, and they can be switched dynamically by
setting multi-function terminals.