Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-48-
Function
code
Name
Description
Default
Modify
this function parameter during running, the VFD
stops and reports the bus undervoltage fault.
Setting range: 0.0V
–500.0V
When the bus voltage is lower than the value of this function parameter during running, the system considers it is in the
undervoltage state, which is not good for the inverter unit to run. Set the value according to the actual application
situation.
Function
code
Name
Description
Default
Modify
P00.05
Overvoltage point for
bus voltage
Overvoltage point for bus voltage for protection
purpose.
When the bus voltage is higher than the value of
this function parameter during running, the VFD
stops and reports the bus overvoltage fault.
Setting range: 500.0V
–850.0V
800.0V
/
When the bus voltage is higher than the value of this function parameter during running, the system considers it is in the
overvoltage state. In the overvoltage state, the rectifier unit keypad blinks. In addition, if the motor is running in the power
generation state, the bus voltage may continuously increase. Set the value according to the actual application situation.
Function
code
Name
Description
Default
Modify
P00.04
Braking start voltage for
the braking unit
Voltage at which the braking unit starts braking.
When the bus voltage reaches the value of this
function parameter during running, the braking
pipe starts braking.
This function is valid only for the models
configured with built-in braking units, invalid for
the models connected to external brakes.
Setting range: 400.0V
–800.0V
700.0V
○
P00.10
Braking pipe direct
connection protection
P00.10 specifies the fault protection mode for the
braking pipe. Mode of protecting the braking pipe
against faults.
0: Disable
1: Enable
Ones place: Braking pipe direct connection
enabling selection.
Tens place: Braking pipe overcurrent enabling
selection.
Hundreds place: Braking pipe overload enabling
selection.
Note: Valid only for the 45kW rectifier unit with
the built-in braking unit.
0x111
◎
If the braking unit has a value higher than P00.04, the braking unit acts to reduce the bus voltage. You need to configure
the external braking resistor according to the actual application. P00.10 specifies the fault protection mode for the
braking pipe in case of direct connection, overcurrent and overload, and it is valid by default. Set the protection mode
according to the actual application.