Goodrive600 series high-performance multifunction VFD
Function parameter list
-300-
Function
code
Name
Description
Default Modify
P13.04
Switch-over frequency
of pull-in current
0.00Hz
–P00.03 (Max. output frequency)
10.00Hz
○
P13.05
Reserved
200Hz
–1000Hz
500Hz
◎
P13.06
High-frequency
superposition voltage
Setting range: 0.0
–300.0% (of the motor rated
voltage)
100.0%
◎
P13.07
Reserved
0.0
–400.0
0.0
○
P13.08
Control parameter 1
0
–0xFFFF
0
○
P13.09
Control parameter 2
Used to set the frequency threshold for enabling
the counter-electromotive force phase-locked
loop in SVC 0. When the running frequency is
lower than the value of the function code, the
phase-locked loop is disabled; and when the
running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0
–655.35
2.00
○
P13.10
Angle compensation
0.0
–359.9
0.0
○
P13.11
Maladjustment detection
time
Used to adjust the responsiveness of
anti-maladjustment function. If the load inertia is
large, increase the value of this parameter
properly, however, the responsiveness may slow
down accordingly.
Setting range: 0.0
–10.0s
0.5s
○
P13.12
High-frequency
compensation
coefficient of SM
Valid when the motor speed exceeds the rated
speed. If oscillation occurred to the motor, adjust
this parameter properly.
Setting range: 0.0
–100.0%
0.0%
○
P13.13
High-frequency
current-loop
0
–200.0%
20.0%
○
P13.19
Reserved
0
–65535
0
○
P14 group
––Communication
Function
code
Name
Description
Default Modify
P14.00
Local communication
address
Setting range: 1
–247
When the master writes the slave
communication address to 0 indicating a
broadcast address in a frame, all the salves on
the Modbus bus receive the frame but do not
respond to it.
The communication addresses on the
communication network are unique, which is the
basis of the point-to-point communication.
Note: The communication address of a slave
cannot be set to 0.
1
○
P14.01
Communication baud
rate
Used to set the data transmission speed
between the upper computer and the inverter
unit.
4
○