Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-53-
Function
code
Name
Default
Setting
range
Description
P05.01
Function of S1
1
0
–9
See the following
table.
P05.02
Function of S2
2
P05.03
Function of S3
0
P05.04
Function of S4
0
P05.05
Function of S5
0
These parameters are used to set the corresponding functions of digital input terminals. The selectable functions are as
follows.
Setting
Function
Description
0
No function
You can set the unused terminals to "no function" to avoid
maloperation.
1
Run
The rectifier unit runs.
2
Fault reset
The terminal is used for fault reset. The function can also be achieved
by using the RESET key on the keypad.
3
External fault
An external fault occurs, displaying the external fault information.
4
Incoming circuit breaker
feedback
The rectifier unit sends a run command to the inverter unit according to
this feedback signal.
5
Auxiliary circuit breaker
feedback
The rectifier unit sends a run command to the inverter unit according to
this feedback signal.
6
Leakage protection
switch feedback
The rectifier unit sends a run command to the inverter unit according to
this feedback signal.
7
Disable the inverter unit
to run
The rectifier unit sends a run prohibition command to the inverter unit
according to this feedback signal.
8
Enable the inverter unit
to coast to stop
The rectifier unit sends a command of coasting to stop to the inverter
unit according to this feedback signal.
9
Enable the inverter unit
to stop in the set manner
The rectifier unit sends a command of stopping in the set manner to
the inverter unit according to this feedback signal.
Note: Two different multifunction input terminals cannot be configured with a same function.
You can set P05.07 to enhance the anti-interference capability in the application scenarios where maloperation may be
caused since input terminals are susceptible to interference. However, increasing the filter time will cause the terminal
response slow-down.
Related function codes are as follows.
Function
code
Name
Description
Default
Modify
P05.06
Input terminal
polarity
Used to set the polarity of input terminals.
When a bit is 0, the input terminal is positive;
when a bit is 1, the input terminal is negative.
BIT4
BIT3
BIT2
BIT1
BIT0
S5
S4
S3
S2
S1
Setting range: 0x000
–0x1F
0x000
○
P05.07
Digital input filter time
Used to set the filter time of sampling for
terminals S1
–S5. In strong interference cases,
increase the value to avoid maloperation.
0.000
–1.000s
0.000s
○
P05.13
S1 switch-on delay Used to specify the delay time corresponding to
0.000s
○