Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-79-
Function
code
Name
Description
Default
1: S curve
Note: If mode 1 is selected, set P01.06,
P01.07, P01.27 and P01.08 accordingly.
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
braking for stop
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P01.10
Wait time before DC braking
for stop
0.00
–50.00s
0.00s
P01.11
DC braking current for stop
0.0
–100.0%
0.0%
P01.12
DC braking time for stop
0.00
–50.00s
0.00s
P01.13
FWD/REV running deadzone
time
0.0
–3600.0s
0.0s
P01.14
FWD/REV running switching
mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0
P01.15
Stop speed
0.00
–100.00Hz
0.50 Hz
P01.16
Stop speed detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
1
P01.18
Terminal-based running
command protection at
power-on
0: The terminal running command is invalid at
power-on
1: The terminal running command is valid at
power-on
0
P01.19
Action selected when running
frequency less than frequency
lower limit (valid when
frequency lower limit greater
than 0)
0: Run at the frequency lower limit
1: Stop
2: Sleep
0
P01.20
Wake-up-from-sleep delay
0.0
–3600.0s (Valid only when P01.19=2)
0.0s
P01.21
Power-off restart selection
0: Disable
1: Enable
0
P01.22
Wait time for restart after
power-off
0.0
–3600.0s (Valid only when P01.21=1)
1.0s
P01.23
Start delay
0.0
–60.0s
0.0s
P01.24
Stop speed delay
0.0
–100.0s
0.0s
P01.25
Open-loop 0Hz output
selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0
P01.26
DEC time for emergency stop 0.0
–60.0s
2.0s
P01.27
Time of starting segment of
DEC S curve
0.0
–50.0s
0.1s
P01.28
Time of ending segment of
DEC S curve
0.0
–50.0s
0.1s
P01.29
Short-circuit braking current
0.0
–150.0% (of the inverter unit reated
current)
0.0%
P01.30
Hold time of short-circuit
braking for start
0.00
–50.00s
0.00s
P01.31
Hold time of short-circuit
0.00
–50.00s
0.00s