Goodrive600 series high-performance multifunction VFD
Function parameter list
-256-
Function
code
Name
Description
Default Modify
P02.24
Reserved
0x0000
–0Xffff
0
●
P02.25
Identification current of
SM 1
0%
–50% (of the motor rated current)
10%
●
P02.26
Overload protection of
motor 1
0: No protection
1: Common motor protection (with low-speed
compensation). As the cooling effect of a
common motor is degraded at low speed
running, the corresponding electronic thermal
protection value needs to be adjusted properly,
the low compensation indicates lowering the
overload protection threshold of the motor whose
running frequency is lower than 30Hz.
2: Variable-frequency motor protection (without
low speed compensation). Because the heat
dissipation function for a variable-frequency
motor is not impacted by the rotation speed, it is
not necessary to adjust the protection value at
low speed running.
2
◎
P02.27
Overload protection
coefficient of motor 1
Motor overload multiples M=Iout/(In*K)
"In" is rated motor current, "lout" is inverter unit
output current, and "K" is motor overload
protection coefficient.
A smaller value of "K" indicates a bigger value of
"M".
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=150%,
protection is performed after motor overload
lasts for 12 minutes; when M=200%, protection
is performed after motor overload lasts for 60
seconds; and when M≥400%, protection is
performed immediately.
1
5
12
60
116%
200%
Time t(min)
Motor overload
multiple
150%
180%
Setting range: 20.0%
–150.0%
100.0%
○
P02.28
Power display calibration
coefficient of motor 1
The function code can be used to adjust the
power display value of motor 1. However, it does
not affect the control performance of the inverter
unit.
Setting range: 0.00
–3.00
1.00
○