Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-68-
Function
code
Name
Description
Default
P04.35
Pull-in current 2 in SM V/F
control
When the SM VF control mode is enabled, the function
parameter is used to set the reactive current of the
motor when the output frequency is greater than the
frequency specified by P04.36.
Setting range: -100.0%
–100.0% (of the motor rated
current)
10.0%
P04.36
Frequency threshold for
pull-in current switching in
SM V/F control
When the SM VF control mode is enabled, the function
parameter is used to set the frequency threshold for
the switching between pull-in current 1 and pull-in
current 2.
Setting range: 0.00Hz
–P00.03 (Max. output frequency)
50.00Hz
P04.37
Reactive current
closed-loop proportional
coefficient in SM V/F
control
When the SM VF control mode is enabled, the function
parameter is used to set the proportional coefficient of
reactive current closed-loop control.
Setting range: 0
–3000
50
P04.38
Reactive current
closed-loop integral time in
SM V/F control
When the SM VF control mode is enabled, the function
parameter is used to set the integral coefficient of
reactive current closed-loop control.
Setting range: 0
–3000
30
P04.39
Reactive current
closed-loop output limit in
SM VF control
When the SM VF control mode is enabled, the function
parameter is used to set the output limit of the reactive
current closed-loop control. A greater value indicates a
higher reactive closed-loop compensation voltage and
higher output power of the motor. In general, you do
not need to modify the function code.
Setting range: 0
–16000
8000
P04.40
Enabling IF mode for AM 1
0: Disable
1: Enable
0
P04.41
Current setting in IF mode
for AM 1
When IF control is adopted for AM 1, the function
parameter is used to set the output current. The value
is a percentage in relative to the rated current of the
motor.
Setting range: 0.0
–200.0%
120.0%
P04.42
Proportional coefficient in
IF mode for AM 1
When IF control is adopted for AM 1, the function
parameter is used to set the proportional coefficient of
the output current closed-loop control.
Setting range: 0
–5000
650
P04.43
Integral coefficient in IF
mode for AM 1
When IF control is adopted for AM 1, the function
parameter is used to set the proportional coefficient of
the output current closed-loop control.
Setting range: 0
–5000
350
P04.44
Starting frequency point for
switching off IF mode for
AM 1
0.00
–P04.50
10.00Hz
P04.45
Enabling IF mode for AM 2
0: Disable
1: Enable
0
P04.46
Current setting in IF mode
for AM 2
When IF control is adopted for AM 2, the function
parameter is used to set the output current. The value
120.0%