Goodrive600 series high-performance multifunction VFD
Function parameter list
-266-
Function
code
Name
Description
Default Modify
10: Reserved
11: EtherCAT/PROFINET communication
12: Programmable expansion card
13: PROFIBUS-DP/DeviceNet communication
P04.28
Voltage set through
keypad
The function parameter is the voltage digital
setting when "keypad" is selected as the voltage
setting channel.
Setting range: 0.0%
–100.0%
100.0%
○
P04.29
Voltage increase time Voltage increase time means the time needed for
the inverter unit to accelerate from min. output
voltage to the max. output frequency.
Voltage decrease time means the time needed
for the inverter unit to decelerate from the max.
output frequency to min. output voltage.
Setting range: 0.0
–3600.0s
5.0s
○
P04.30
Voltage decrease time
5.0s
○
P04.31
Max. output voltage
Used to set the upper and lower limits of output
voltage.
Vmax
Vmin
Vset
Time t
t1
t2
t1=P04.29
t2=P04.30
–100.0% (of the
motor rated voltage)
P04.32 setting range: 0.0%
100.0%
◎
P04.32
Min. output voltage
0.0%
◎
P04.33
Weakening coefficient in
constant power zone
1.00
–1.30
1.00
○
P04.34
Pull-in current 1 in SM
VF control
-100.0%
–100.0% (of the motor rated current)
20.0%
○
P04.35
Pull-in current 2 in SM
VF control
-100.0%
–100.0% (of the motor rated current)
10.0%
○
P04.36
Frequency threshold for
pull-in current switching
in SM V/F control
0.00Hz
–P00.03 (Max. frequency)
50.00Hz
○
P04.37
Reactive current
closed-loop proportional
coefficient in SM V/F
control
0
–3000
50
○
P04.38
Reactive current
closed-loop integral time
in SM V/F control
0
–3000
30
○
P04.39
Reactive current
closed-loop output limit
in SM VF control
0
–16000
8000
○
P04.40
Enabling IF mode for
AM 1
0
–1
0
◎