Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-67-
Function
code
Name
Description
Default
P04.17
V/F voltage point 1 of
motor 2
0.0%
–110.0%
0.0%
P04.18
V/F frequency point 2 of
motor 2
P04.16
– P04.20
0.00Hz
P04.19
V/F voltage point 2 of
motor 2
0.0%
–110.0%
0.0%
P04.20
V/F frequency point 3 of
motor 2
P04.18
–P02.02 or P04.18–P02.16
0.00Hz
P04.21
V/F voltage point 3 of
motor 2
0.0%
–110.0%
0.0%
P04.22
V/F slip compensation gain
of motor 2
0.0
–200.0%
100.0%
P04.23
Low-frequency oscillation
control factor of motor 2
0
–100
10
P04.24
High-frequency oscillation
control factor of motor 2
0
–100
10
P04.25
Oscillation control
threshold of motor 2
0.00Hz
–P00.03 (Max. output frequency)
30.00Hz
P04.26
Energy-saving run
0: Disable
1: Automatic energy-saving run
0
P04.27
Voltage setting channel
0: Keypad (The output voltage is determined by
P04.28.)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Multi-step speed running (The setting is determined
by group P10.)
6: PID
7: Modbus communication
8: CANopen communication
9: Ethernet communication
10: Reserved
11: EtherCAT/PROFINET communication
12: Programmable expansion card
13: PROFIBUS-DP/DeviceNet communication
0
P04.28
Voltage set through keypad 0.0%
–100.0% (of the motor rated voltage)
100.0%
P04.29
Voltage increase time
0.0
–3600.0s
5.0s
P04.30
Voltage decrease time
0.0
–3600.0s
5.0s
P04.31
Max. output voltage
P04.32
–100.0% (of the motor rated voltage)
100.0%
P04.32
Min. output voltage
0.0%
–P04.31 (Motor rated voltage)
0.0%
P04.34
Pull-in current 1 in SM V/F
control
When the SM VF control mode is enabled, the function
parameter is used to set the reactive current of the
motor when the output frequency is lower than the
frequency specified by P04.36.
Setting range: -100.0%
–100.0% (of the motor rated
current)
20.0%