Goodrive600 series high-performance multifunction VFD
Communication networking
-137-
6.4.2 Networking description
In this networking mode, the rectifier unit is configured to work as the CANopen slave node, the PLC is configured as the
master node. The CANopen slave node, baud rate, communication disconnection enabling, and PDO interaction data
are configured on the rectifier/inverter unit through function codes.
6.4.3 Related parameters
Table 6-5 Rectifier unit related parameters
Function
code
Name
Description
Default
Modify
P21.01
CANopen
communication address
0
–127
1
○
P21.13
Sent PZD2
Used when the rectifier unit works as the
CANopen slave node or used in
PLC-to-CANopen networking.
0: Invalid
1: Fault code
2: DC voltage (* 10, V)
3: Grid voltage (* 1, V)
4: Grid frequency (* 10, Hz)
5: Braker current (* 10, A)
6: Terminal input status
7: Terminal output status
8: Number of online slave nodes
9: Online/offline state of slave nodes 02
–
17
10: Online/offline state of slave nodes
18
–21
11: CANopen bus load rate
12: Type of card at slot 1
13: Type of card at slot 2
14: Software version of card at slot 1
15: Software version of card at slot 2
16: R-phase current
17: S-phase current
18: T-phase current
19: Node number of first CANopen offline
unit
20: Reserved
0
○
P21.14
Sent PZD3
0
○
P21.15
Sent PZD4
0
○
P21.16
Sent PZD5
0
○
P21.17
Sent PZD6
0
○
P21.18
Sent PZD7
0
○
P21.19
Sent PZD8
0
○
P21.20
Sent PZD9
0
○
P21.21
Sent PZD10
0
○
P21.22
Sent PZD11
0
○
P21.23
Sent PZD12
0
○
P21.29
CANopen
communication baud
rate
Setting range: 0
–5
0: 50Kbps
1: 100 Kbps
2: 125Kbps
3: 250Kbps
4: 500Kbps
5: 1M bps
3
○
P21.30
CANopen
communication timeout
time
0.0 (invalid); 0.1
–100.0s
0.0s
○