Goodrive600 series high-performance multifunction VFD
Communication networking
-155-
Table 6-22 Objects with the control function in the manufacturer-defined object dictionary
Index
(hex)
Subindex
(hex)
Function
Access
permission
Data
length
Corresponding to
2100
0
Request code (Do not use)
RW
2 Byte
/
1
Parameter address (Do not use)
RW
2 Byte
/
2
Request data (Do not use)
RW
2 Byte
/
3
Setting1
RW
2 Byte
Received PZD2
4
Setting2
RW
2 Byte
Received PZD3
5
Setting3
RW
2 Byte
Received PZD4
6
Setting4
RW
2 Byte
Received PZD5
7
Setting5
RW
2 Byte
Received PZD6
8
Setting6
RW
2 Byte
Received PZD7
9
Setting7
RW
2 Byte
Received PZD8
A
Setting8
RW
2 Byte
Received PZD9
B
Setting9
RW
2 Byte
Received PZD10
C
Setting10
RW
2 Byte
Received PZD11
D
Setting11
RW
2 Byte
Received PZD12
E
Reserved
RW
2 Byte
/
F
Reserved
RW
2 Byte
/
2101
0
CW
RW
2 Byte
/
Table 6-23 Objects with the monitoring function in the manufacturer-defined object dictionary
Index
(hex)
Subindex
(hex)
Function
Access
permission
Data
length
Corresponding to
2000
0
Response code (Do not use)
RO
2 Byte
/
1
Error code (Do not use)
RO
2 Byte
/
2
Response data (Do not use)
RO
2 Byte
/
3
Returned value1
RO
2 Byte
Sent PZD2
4
Returned value2
RO
2 Byte
Sent PZD3
5
Returned value3
RO
2 Byte
Sent PZD4
6
Returned value4
RO
2 Byte
Sent PZD5
7
Returned value5
RO
2 Byte
Sent PZD6
8
Returned value6
RO
2 Byte
Sent PZD7
9
Returned value7
RO
2 Byte
Sent PZD8
A
Returned value8
RO
2 Byte
Sent PZD9
B
Returned value9
RO
2 Byte
Sent PZD10
C
Returned value10
RO
2 Byte
Sent PZD11
D
Returned value11
RO
2 Byte
Sent PZD12
E
Reserved
RO
2 Byte
/
F
Reserved
RO
2 Byte
/
2001
0
SW
RO
2 Byte
/
Example
Example 1: To instruct the VFD whose address is 3 to run forwardly, the master node transmits the following SDO
command.