Goodrive600 series high-performance multifunction VFD
Communication networking
-212-
Ensure that the electrical wiring is correct and
secure.
Power on.
The panel data display is normal.
Restore to factory settings.
Set the command channel
Set the DP slave address.
Start
Set the PZD receiving/sending options.
Perform configuration on the upper computer.
Download and run the PLC user program.
Stop.
The commissioning is completed.
Rectifier: P00.14=1
Inverter: P00.18=1
Rectifier: Group
P22
Inverter: Group P15
Group P00
Rectifier: Group
P22
Inverter: Group P15
Figure 6-11 Commissioning procedure
6.7.4.2 TIA portal configuration (S7-300)
For details, see 6.5.6.2 TIA portal configuration (S7-300).
Note:
There is difference in the salve device configuration between the PROFIBUS-DP bus networking and
PROFIBUS-DP-to-CANopen networking:
In the PROFIBUS-DP-to-CANopen network, each device needs to be configured with a certain number of slots, which
depends on the number of CANopen slave nodes. In the PROFIBUS-DP bus network, many PROFIBUS-DP devices are
added, and only a slot module needs to be configured for each of the device.