Goodrive600 series high-performance multifunction VFD
Function parameter list
-264-
Function
code
Name
Description
Default Modify
P04.06
V/F voltage point 2 of
motor 1
overheat or damage and cause VFD
overcurrent stall or overcurrent protection.
Output voltage
Output
frequency(Hz)
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
P04.03 setting range: 0.00Hz
P04.04 setting range: 0.0%
–110.0% (of the rated
voltage of motor 1)
P04.06 setting range: 0.0%
–110.0% (of the rated
voltage of motor 1)
frequency of AM 1) or P04.05
frequency of SM 1)
P04.08 setting range: 0.0%
–110.0% (of the rated
voltage of motor 1)
0.0%
○
P04.07
V/F frequency point 3 of
motor 1
0.00Hz
○
P04.08
V/F voltage point 3 of
motor 1
00.0%
○
P04.09
V/F slip compensation
gain of motor 1
Used to compensate for the motor rotating speed
change caused by load change in the space
voltage vector mode, and thus improve the
rigidity of the mechanical characteristics of the
motor. You need to calculate the rated slip
frequency of the motor as follows:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor,
corresponding to function code P02.02. n is the
rated rotating speed of the motor, corresponding
to function code P02.03. p is the number of pole
pairs of the motor. 100.0% corresponds to the
rated slip frequency
△
f of the motor.
Setting range: 0.0
–200.0%
0.0%
○
P04.10
Low-frequency
oscillation control factor
of motor 1
In space voltage vector control mode, the motor,
especially the large-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable motor
running, or even inverter unit overcurrent. You
can adjust the two function parameters properly
to eliminate such phenomenon.
P04.10 setting range: 0
–100
P04.11 setting range: 0
–100
P04.12 setting range: 0.00Hz
–P00.03 (Max.
output frequency)
10
○
P04.11
High-frequency
oscillation control factor
of motor 1
10
○
P04.12
Oscillation control
threshold of motor 1
30.00Hz
○
P04.13
V/F curve setting of
motor 2
0: Straight-line V/F curve
1: Multi-point V/F curve
0
◎