Goodrive600 series high-performance multifunction VFD
Communication networking
-219-
Ensure the electrical wiring is correct and secure.
Power on.
The panel data display is normal.
Restore to factory settings.
Set the command channel.
Set the PROFINET communication timeout time.
Start
Set the PZD receiving and sending options.
Perform configuration on the upper computer.
Download and run the PLC user program.
Stop.
The commissioning is completed.
Rectifier: P00.14=1
Inverter: P00.18=1
Rectifier : Group P00
Inverter: Groups P00 and
P03
Rectifier: P22.26
Inverter: P16.31
Rectifier: Group P23
Inverter: Group P16
Figure 6-14 Commissioning procedure
6.8.4.2 TIA portal configuration (S7-1500)
For details, see 6.6.5.2 TIA portal configuration (S7-1500).
Note:
There is difference in the salve device configuration between the PROFINET bus networking and
PROFINET-to-CANopen networking:
In the PROFINET-to-CANopen network, each device needs to be configured with a certain number of slots, which
depends on the number of CANopen slave nodes. In the PROFINET bus network, many PROFINET devices are added,
and only a slot module needs to be configured for each of the device.