Goodrive600 series high-performance multifunction VFD
Function parameter list
-299-
Function
code
Name
Description
Default Modify
1
5
12
60
116%
200%
Time t(min)
Motor overload
multiple
150%
180%
Setting range: 20.0%
–120.0%
P12.28
Power display
calibration coefficient of
motor 2
0.00
–3.00
1.00
○
P12.29
Parameter display
selection of motor 2
0: Display by motor type. In this mode, only
parameters related to the present motor type are
displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0
○
P12.30
System inertia of motor
2
0.000
○
P12.31
–
P12.32
Reserved
0
–65535
0
○
P13 group
––SM control
Function
code
Name
Description
Default Modify
P13.00
Reduction rate of the
injection current of SM
Setting range: 0.0%
–100.0% (of the motor rated
current)
80.0%
○
P13.01
Detection mode of initial
pole
0: Not detect
1: High-frequency superposition
2: Pulse superposition
0
◎
P13.02
Pull-in current 1
Pull-in current is the pole position orientation
current; pull-in current 1 is valid within the lower
limit of pull-in current switch-over frequency
threshold. If you need to increase the start
torque, increase the value of this function
parameter properly.
Setting range: 0.0%
–100.0% (of the motor
rated current)
20.0%
○
P13.03
Pull-in current 2
Pull-in current is orientation current of the pole
position; pull-in current 2 is valid within the upper
limit of pull-in current switch-over frequency
threshold, and you do not need to change pull-in
current 2 under common situations.
Setting range: 0.0%
–100.0% (of the motor rated
current)
10.0%
○