Goodrive600 series high-performance multifunction VFD
Optional peripheral accessories
-405-
Inverter unit model
Output reactor
GD600-51-015-4
OCL2-015-4
GD600-51-018-4
OCL2-018-4
GD600-51-022-4
OCL2-022-4
GD600-51-030-4
OCL2-037-4
GD600-51-037-4
OCL2-037-4
GD600-51-045-4
OCL2-045-4
GD600-51-055-4
OCL2-055-4
GD600-51-075-4
OCL2-075-4
Note:
The rated input voltage drop of input reactors is 2%±15%.
The rated output voltage drop of output reactors is 1%±15%.
The preceding table describes external accessories. You need to specify the ones you choose when purchasing
accessories.
E.7 Filter
EMC screws are connected in factory for the rectifier unit products, all of which meet the requirements of level C3.
Note:
Disconnect EMC screw in the following situations:
1. The EMC filter is applicable to the neutral-grounded grid system. If it is used for the IT grid system (that is, non-neutral
grounded grid system), disconnect EMC screws (M3: tightening torque 5
–6 kgf.cm).
2. If leakage protection occurs during configuration of a residual-current circuit breaker, disconnect EMC screws (M3:
tightening torque 5
–6 kgf.cm).
Bottom
Note: Do not connect C3 filters in IT power systems.
Interference filters on the input side can reduce the VFD interference on the surrounding devices.
Noise filters on the output side can decrease the radio noise caused by the cables between VFDs and motors and the
leakage current of conducting wires.