Goodrive600 series high-performance multifunction VFD
Function parameter list
-236-
Function
code
Name
Description
Default Modify
rectifier unit.
Range: 0.0
–120.0 Hz
P17.07
Grid voltage
Used to display the present grid voltage of the
inverter.
Range: 0.0
–2000.0 V
0.0V
●
P17.08
3PH voltage unbalance
factor
Used to display the factor of imbalanced
three-phase voltage of the grid.
Range: 1.00
–10.0
0.0
●
P17.09
Braking pipe module
temperature
Used to display the braking pipe module
temperature.
Range: -20.0
–120.0°C
Note: Valid only for the 45kW rectifier unit
model.
0.0°C
●
P17.10
Rectifier bridge
temperature
Used to display the rectifier bridge temperature.
Range: -20.0
– 120.0°C
0.0°C
●
P17.11
3PH AC voltage
Used to display the AC input current of the
rectifier unit.
Range: 0.0
–1000.0A
The 160kW and 355kW rectifier unit models
support the use of the optional current detection
module.
0.0A
●
P17.12
Digital input terminal
status
Used to display the present digital input terminal
status of the rectifier unit.
Range: 0000
–00FF
BIT4
BIT3
BIT2
BIT1
BIT0
S5
S4
S3
S2
S1
0
●
P17.13
Digital output terminal
status
Used to display the present digital output terminal
status of the rectifier unit.
Range: 0000
–0003
BIT1
BIT0
RO2
RO1
0
●
P17.14
Brake current
Used to display the current of the brake.
Range: 0.0
–6000.0A
Only the 45kW rectifier unit model has the built-in
braking unit. Other rectifier unit models support
only external braking units, and the displayed
value is invalid for these models.
0.0A
●
P17.15
Actual online slave
nodes
Number of actual online slave nodes.
Range: 0
–20
0
●
P17.16
Type of card at slot 1 Used to display the type of card at the slot.
Range: 0
–18
0: No card
1: PLC
2: I/O
3
–4: Reserved
5: Ethernet
6: PROFIBUS-DP
0
●
P17.17
Type of card at slot 2
0
●