Goodrive600 series high-performance multifunction VFD
Communication networking
-220-
6.8.4.3 IN/OUT module mapping
In the configuration of PROFINET bus communication, IN/OUT modules can support the selection of only 16 words,
which support the reading and writing of function codes. To be specific, mapping from PKW, an IN/OUT module supports
data reading and writing of up to 11 PZDs (PZD2
–PZD12).
6.8.5 Related parameters
Table 6-45 Rectifier unit related parameters
Function
code
Name
Description
Default Modify
P00.01
Channel of running
commands
Used to select the channel of rectifier unit control
commands, including the start, stop, and fault
reset commands.
The running commands are controlled through
keypad keys, such as RUN and STOP/RST.
1: Terminal
The running commands such as run, stop, and
fault reset are controlled through multi-function
input terminals.
2: Communication
The running commands are controlled by the
upper computer in communication mode.
1
○
P00.02
Communication mode
of running commands
Used to select the rectifier unit communication
command mode.
0: RS485
1: CANopen
2: PLC
3: PROFIBUS-DP
4: PROFINET/EtherCAT
0
○
P17.16
Type of card at slot 1 Used to display the type of card at the slot.
Range: 0
–18
0: No card
1: PLC
2: I/O
3
–4: Reserved
5: Ethernet
6: PROFIBUS-DP
7: Reserved
8: Reserved
9: Reserved
10: Reserved
11
–14: Reserved
15: PROFINET
16: Modbus
17: EtherCAT
18: BACnet
0
●
P17.17
Type of card at slot 2
0
●
P17.18
Software version of card
at slot 1
Used to display the software version of thecard at
slot 1.
Range: 0
–655.35
0.00
●