Goodrive600 series high-performance multifunction VFD
Function parameter list
-277-
Function
code
Name
Description
Default Modify
If you set the function code to 00000, the
previous user password is cleared and password
protection is disabled.
After the user password is set and takes effect,
you cannot enter the parameter menu if you
enter an incorrect password. Please remember
your password and save it in a secure place.
After you exit the function code editing interface,
the password protection function is enabled
within 1 minute. If password protection is
enabled, "0.0.0.0.0" is displayed when you press
the PRG/ESC key again to enter the function
code editing interface. You need to enter the
correct user password to enter the interface.
Note: Restoring the default values may delete
the user password. Exercise caution when
using this function.
P07.01
Reserved
0
–65535
0
●
P07.02
Function of QUICK/JOG
Range: 0x00
–0x27
Ones place: Function of QUICK/JOG
0: No function
1: Jog
2: Reserved
3: Switch between forward and reverse rotating
4: Clear the UP/DOWN setting
5: Coast to stop
6: Switch command channels in sequence
7: Reserved
Tens place: Reserved
0x01
◎
P07.03
Reserved
0
–65535
0
●
P07.04
Stop function validity of
STOP/RST
0: Valid only for keypad control
1: Valid both for keypad and terminal control
2: Valid both for keypad and communication
control
3: Valid for all control modes
0
○
P07.05
Selection 1 of
parameters to be
displayed in the running
state
0x0000
–0xFFFF
Bit 0: Running frequency (Hz on)
Bit 1: Set frequency (Hz blinking)
Bit 2: Bus voltage (V on)
Bit 3: Output voltage (V on)
Bit 4: Output current (A on)
Bit 5: Running speed (rpm on)
Bit 6: Output power (% on)
Bit 7: Output torque (% on)
Bit 8: PID reference value (% blinking)
Bit 9: PID feedback value (% on)
Bit 10: Input terminal state
Bit 11: Output terminal state
0x03FF
○