Goodrive600 series high-performance multifunction VFD
Function parameter list
-249-
Function
code
Name
Description
Default Modify
Advantage of high carrier frequency: ideal
current waveform, little current harmonic wave
and motor noise.
Disadvantage of high carrier frequency:
increasing the switch loss, increasing inverter
unit temperature and the impact to the output
capacity. The inverter unit needs to derate on
high carrier frequency. At the same time, the
leakage and electrical magnetic interference will
increase.
On the contrary, an extremely-low a carrier
frequency may cause unstable operation at low
frequency, decrease the torque, or even lead to
oscillation.
The carrier frequency has been properly set in
the factory before the inverter unit is delivered
from the factory. In general, you do not need to
modify it.
When the frequency used exceeds the default
carrier frequency, the VFD needs to derate by
10% for each increase of 1k carrier frequency.
Setting range: 1.2
–15.0kHz
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter autotuning. It is
recommended to use rotating autotuning when
high control accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in cases
where the motor cannot be disconnected from
load.
3: Static autotuning 2 (partial autotuning); when
the present motor is motor 1, only P02.06,
P02.07, and P02.08 are autotuned; when the
present motor is motor 2, only P12.06, P12.07,
and P12.08 are autotuned.
4: Rotary autotuning 2, which is similar to rotary
autotuning 1 but only valid for AMs.
5: Static autotuning 3 (partial autotuning), which
is valid only for AMs.
0
◎
P00.16
AVR function selection
0: Invalid
1: Valid during the whole procedure
Automatic voltage regulation function is used to
eliminate the bus voltage fluctuation impact on
the inverter unit output voltage.
1
○
P00.18
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
0
◎