Goodrive600 series high-performance multifunction VFD
Communication networking
-165-
Step 4. Configure the slave node.
Double-click the INVT-6SE70-GW icon in the project to enter the slave node parameter setting view. Click
Slave_1
to
enter the PROFIBUS slave node configuration interface. Click the
General
tab, choose
PROFIBUS addresses
, and set
parameters.
IO module address types are classified into default and customized address types. To select the default address type, on
the
General
tab, click
Device-specific parameters
, select
Default Address
from
CANopen Address type
.
The IO module addresses increase by 1 in ascending order. To be specific, the data of IO module 1 corresponds to
CANopen node 1, the data of IO module 2 corresponds to CANopen node 2, and so on.
I address
and
Q address
indicate the receiving and sending addresses of the node. Slot 1 corresponds to the data of the rectifier unit master node,
while slots 2 to 21 correspond to the data of inverter unit slave nodes, which means 20 slave nodes can be supported at
most. Click
Hardware catalog
, and double-click a module or drag it to the device view to set the data receiving length for
the module.