Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-94-
Setting
Function
Description
to the pulse speed set by P21.27.
68
Enable pulse superposition
Pulse increment and pulse decrement can be valid only after pulse
superimposition is enabled.
69
Decrease pulses
When the signal is valid, the pulse counting is decreased
according to the pulse speed set by P21.27.
70
Electronic gear selection
When the signal is valid, select the numerator of the position
command set by P21.30. When it is invalid, the numerator of the
position command is decided by P21.11.
71
Switch to the master
When the function is enabled in stopped state, the unit switches to
the master mode.
72
Switch to the slave
When the function is enabled in stopped state, the unit switches to
the slave mode.
73
–79
Reserved
/
Related parameter list:
Function
code
Name
Description
Default
P05.01
Function of S1
0: No function
1: Run forward
2: Run reversely
3: Three-wire running control
4: Jog forward
5: Jog reversely
6: Coast to stop
7: Reset faults
8: Pause running
9: External fault input
10: Increase frequency setting (UP)
11: Decrease frequency setting (DOWN)
12: Clear the frequency increase/decrease
setting
13: Switch between A setting and B setting
14: Switch between combination setting and A
setting
15: Switch between combination setting and B
setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Pause multi-step speed running
21: ACC/DEC time selection 1
22: ACC/DEC time selection 2
23: Simple PLC stop reset
24: Pause simple PLC
25: Pause PID control
26: Limit on forward running
27: Limit on reverse running
28: Counter reset
1
P05.02
Function of S2
4
P05.03
Function of S3
7
P05.04
Function of S4
0
P05.05
Reserved
0
P05.06
Reserved
0
P05.07
Reserved
0