CHAPTER 7: IEC 61850 PROTOCOL
7.1 IEC 61850 GENERIC SUBSTATION STATE EVENT (GSSE)
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
7-3
Figure 7-1: Remote communication
Default Value
(1 to 32) selects the logic state for this point if the local relay has just completed startup or the remote device
sending the point is declared to be non-communicating. The following choices are available:
•
ON value defaults the input to Logic 1.
•
OFF value defaults the input to Logic 0.
•
Latest OFF freezes the input in case of lost communications. If the latest state is not known, such as after relay power-
up but before the first communication exchange, the input defaults to Logic 0. When communication resumes, the
input becomes fully operational.
•
Latest ON freezes the input in case of lost communications. If the latest state is not known, such as after relay power-
up but before the first communication exchange, the input defaults to Logic 1. When communication resumes, the
input becomes fully operational.
Destination MAC Data (1 to 3)
: If a valid multicast Ethernet MAC address is entered, this address is used as the destination
MAC address for GSSE messages. If a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00),
the device uses the source Ethernet MAC address as the destination, with the multicast bit set.
GSSE RemDevice (1 to 24) MAC Data (1 to 3)
is used to filter receiving messages.
GSSE PORT
sets the network port through messaging will be done. Possible values are "Port A", "Port B" or "Both".
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...