![GE Multilin F650 Instruction Manual Download Page 96](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_572016096.webp)
4-16
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
4.1 ENERVISTA 650 SETUP SOFTWARE
CHAPTER 4: INTERFACES, SETTINGS & ACTUAL VALUES
Option to print the relay configuration using the PC default (active) printer on port COMx or LPT. This option is active only in
offline mode and in file edition (not in online mode while connected to the relay).
Print to file (*xls)
Option to export the configuration file to an Excel file.
4.1.6.5 Compare to settings file
This tool provides an automatic comparison of two different configuration files, or of an online unit to one settings file.
Open the source *.650 file and select the version and model to compare against. The results of the comparison are
displayed as shown:
Figure 4-9: Compare to settings file
4.1.6.6 PLC checksum calculation
When working in offline mode, the PLC Checksum calculation option calculates the CRC of the PLC equations and Relay
configuration section for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated PLC Checksum and
the actual value of the PLC Checksum read from the relay (
Actual values > Status > System Info
) must match.
In order to calculate this checksum, the following sections of the * .650 file are considered:
•
All equations compiled in the file and located in EnerVista 650 Setup
Setpoint > Logic configuration
•
Configuration available in the file and located in EnerVista 650 Setup
Setpoint > Relay configuration
, excluding:
–
HMI tab configuration
–
All configured text
–
Opening and closing time in the Switchgear section
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...