APPENDIX B: MODBUS PROTOCOL
B.5 MEMORY MAP
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
B-141
0x414F
Confirmation address
W
1
Ajustes Derivada de Frecuencia 2-Frequency Rate of Change 2 Settings
0x4150
Function
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x4151
Freq. Rate Trend
F012
1,000 R/W
1
0=INCREASING
1=DECREASING
2=BI-DIRECTIONAL
0x4152
Freq. Rate Pickup
F003
1,000 R/W
2
[0.10 , 10.00] Hz/s
0x4154
Freq. Rate OV Supv
F003
1,000 R/W
2
[0.00 , 110.00] %
0x4156
Freq. Rate Min
F003
1,000 R/W
2
[20.00 , 80.00] Hz
0x4158
Freq. Rate Max
F003
1,000 R/W
2
[20.00 , 80.00] Hz
0x415A
Freq. Rate Delay
F003
1,000 R/W
2
[0.00 , 60.00] s
0x415C
Snapshot Events
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x416F
Confirmation address
W
1
Ajustes Derivada de Frecuencia 3-Frequency Rate of Change 3 Settings
0x4170
Function
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x4171
Freq. Rate Trend
F012
1,000 R/W
1
0=INCREASING
1=DECREASING
2=BI-DIRECTIONAL
0x4172
Freq. Rate Pickup
F003
1,000 R/W
2
[0.10 , 10.00] Hz/s
0x4174
Freq. Rate OV Supv
F003
1,000 R/W
2
[0.00 , 110.00] %
0x4176
Freq. Rate Min
F003
1,000 R/W
2
[20.00 , 80.00] Hz
0x4178
Freq. Rate Max
F003
1,000 R/W
2
[20.00 , 80.00] Hz
0x417A
Freq. Rate Delay
F003
1,000 R/W
2
[0.00 , 60.00] s
0x417C
Snapshot Events
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x418F
Confirmation address
W
1
Inversión de carga 1-Load Encroachment 1
0x4190
Function
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x4191
Min. Voltage
F003
1,000 R/W
2
[0.00 , 300.00] V
0x4193
Reach
F003
1,000 R/W
2
[0.02 , 250.00] Ohm
0x4195
Angle
F003
1,000 R/W
2
[5 , 50] Deg
0x4197
Pickup Delay
F003
1,000 R/W
2
[0.000 , 65.535] s
0x4199
Reset Delay
F003
1,000 R/W
2
[0.000 , 65.535] s
0x419B
Snapshot Events
F012
1,000 R/W
1
0=DISABLED
1=ENABLED
0x41AE
Confirmation address
W
1
Inversión de carga 2-Load Encroachment 2
0x41AF
Function
F012
1,000 R/W
1
0=DISABLED
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...