I-22
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
I.1 FACTORY DEFAULT SETTINGS
APPENDIX I: FACTORY DEFAULT CONFIGURATION
Lowset pickup level
Lowset Pickup
2.00
0.01
A
[0.05 : 160.00]
Internal arc pickup level
Internal Arc Pickup
0.10
0.01
A
[0.05 : 160.00]
Internal arc time delay
Internal Arc Delay
10.00
0.01
s
[0.00 : 900.00]
Retrip time delay
Supervision Delay
10.00
0.01
s
[0.00 : 900.00]
Hiset time delay
HiSet Delay
10.00
0.01
s
[0.00 : 900.00]
Lowset time delay
LowSet Delay
10.00
0.01
s
[0.00 : 900.00]
Second stage time delay
2nd Step Delay
10.00
0.01
s
[0.00 : 900.00]
WITHOUT current element time delay
No Current Delay
10.00
0.01
s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > VT Fuse Failure)
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > BROKEN CONDUCTOR
Broken Conductor 1 > Broken Conductor 2 > Broken Conductor 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Tap Level in percentage of I2/I1
Tap
20
0.10
%
[20.0 : 100.0]
Trip Time
Trip Delay
60
0.01
s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Current Inhibition Level setting
Operation Threshold
0.005
0.00
1 A
[0.000 : 1.000]
Setpoint > Control Elements > Locked Rotor
Locked Rotor 1 > Locked Rotor 2 > Locked Rotor 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A [PHASOR – RMS]
Full load current
Full Load Current
0.50
KA
[0.10 : 10.00]
Pickup level
Pickup Level
1.01
N/A [1.01 : 109.00]
Trip time
Trip Delay
0.00
s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP RANGE
USER
VALUE
Pulse counter enabling setting
CntPulses Enabled X
DISABLED
N/A [DISABLED – ENABLED]
Name of the pulse counter
CntPulses Name X
Pulse Counter 1
N/A N/A
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...