![GE Multilin F650 Instruction Manual Download Page 1025](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_5720161025.webp)
APPENDIX I: FACTORY DEFAULT CONFIGURATION
I.1 FACTORY DEFAULT SETTINGS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
i-21
Setpoint > Control Elements > Synchrocheck
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Dead bus voltage level
Dead Bus Level
10.00
0.01
V
[0.00 : 300.00]
Live bus voltage level
Live Bus Level
50.00
0.01
V
[0.00 : 300.00]
Dead line voltage level
Dead Line Level
10.00
0.01
V
[0.00 : 300.00]
Live line voltage level
Live Line Level
50.00
0.01
V
[0.00 : 300.00]
Voltage Difference
Max Volt Difference
10.00
0.01
V
[2.00 : 300.00]
Angle Difference
Max Angle Difference 10.0
0.1
Deg [2.0 : 80.0]
Frequency Slip
Max Freq Difference
20
10
mHz [10 : 5000]
Breaker Closing time
Time
0.50
0.01
s
[0.01 : 600.00]
Dead Line – Dead Bus Function permission DL-DB Function
DISABLED
N/A [DISABLED – ENABLED]
Live Line – Dead Bus Function permission
LL-DB Function
DISABLED
N/A [DISABLED – ENABLED]
Dead Line – Live Bus Function permission
DL-LB Function
DISABLED
N/A [DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > Autoreclose
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Maximum Number of shots
Max Number Shots
1
N/A [1 : 4]
Dead time 1
Dead Time 1
0.00
0.01
s
[0.00 : 900.00]
Dead time 2
Dead Time 2
0.00
0.01
s
[0.00 : 900.00]
Dead time 3
Dead Time 3
0.00
0.01
s
[0.00 : 900.00]
Dead time 4
Dead Time 4
0.00
0.01
s
[0.00 : 900.00]
Reclaim time or reset lockout delay
Reclaim Time
0.00
0.01
s
[0.00 : 900.00]
Reclose conditions permission
Cond. Permission
DISABLED
N/A [DISABLED – ENABLED]
Hold time
Hold Time
0.00
0.01
s
[0.00 : 900.00]
Reset time
Reset Time
0.00
0.01
s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > breaker failure
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Supervision (retrip) pickup level
Supervision Pickup
1.00
0.01
A
[0.05 : 160.00]
Hiset pickup level
Hiset Pickup
5.00
0.01
A
[0.05 : 160.00]
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...