![GE Multilin F650 Instruction Manual Download Page 461](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_572016461.webp)
CHAPTER 7: IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR F650
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
7-55
2.5.1.2 vinGGIO
This logical node class is used is used to map the latched and self reset virtual Inputs.
Note:
Double control points operate on pairs of Virtual Inputs in a manner that one Virtual Input of the pair is set to “1” and the
other Virtual Input of the pair is set to "0".
For all controllable attributes in this logical node only "direct-control-with-normal-security" model of control is applicable.
GGIO class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
GGIO
Generic process I/O
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Controls
DPCSO1
geDPC
Double point controllable status
output
O
Latched Virtual Input 1, 2
DPCSO2
geDPC
Double point controllable status
output
O
Latched Virtual Input 3, 4
..
..
..
..
..
DPCSO16
geDPC
Double point controllable status
output
O
Latched Virtual Input 31, 32
SPCSO1
SPC
Single point controllable status
output
O
Latched Virtual Input 1
SPCSO2
SPC
Single point controllable status
output
O
Latched Virtual Input 2
..
..
..
..
..
SPCSO32
SPC
Single point controllable status
output
O
Latched Virtual Input 32
SPCSO33
SPC
Single point controllable status
output
O
Self reset Virtual Input 1
SPCSO34
SPC
Single point controllable status
output
O
Self reset Virtual Input 2
..
..
..
..
..
SPCSO64
SPC
Single point controllable status
output
O
Self reset Virtual Input 32
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...