7-206
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
7.2 IEC 61850 PROFILE FOR F650
CHAPTER 7: IEC 61850 PROTOCOL
10 PIXIT for Control model
Gs9
1, 2
Are subscribed GOOSE with test=T (Ed1) / simulation=T (Ed2)
accepted in test/simulation mode
N
Gs10
2
What is the behaviour when a subscribed GOOSE message with
TAL = 0 is received by the subscriber.
The message is ignored. The mechanism
applies where the new GOOSE message is not
received within a TAL.
Gs11
2
What is the behaviour when a subscribed GOOSE message hasn’t
the expected data structure.
The message is ignored. The mechanism
applies where the new GOOSE message is not
received within a TAL.
ID
Ed
Description
Value / Clarification
Ct1
-
What control models are supported
(compare PICS)
Deprecated
Ct2
1, 2
Is the control model fixed, configurable and/or dynamic
Configurable & Dynamic
Ct3
-
Is TimeActivatedOperate supported (compare PICS or SCL)
Deprecated
Ct4
-
Is “operate-many” supported (compare sboClass)
Deprecated
Ct5
1
Will the DUT activate the control output when the test attribute is set
in the SelectWithValue and/or Operate request (when N test
procedure Ctl2 is applicable)
N
Ct6
-
What are the conditions for the time (T) attribute in the SelectWithValue
and/or Operate request
Deprecated
Ct7
-
Is pulse configuration supported (compare pulseConfig)
Deprecated
Ct8
1, 2
What is the behaviour of the DUT when the check conditions are set
Is this behaviour fixed, configurable, online changeable
N synchrocheck
N interlock-check
DUT ignores the check value and always
perform the check
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...