10-6
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
10.8 VERIFICATION OF MEASUREMENT
CHAPTER 10: COMMISSIONING
10.8 Verification of measurement
Set the relay as follows
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE PHASOR ONES
10.8.1 Voltages
Apply the following voltage and frequency values to the relay:
Verify that the relay measures the values with an error of ±1 % of the applied value from 10V to 208V.
10.8.2 Phase currents
Apply the following current and frequency values to the relay:
Verify that the relay measures the values with an error lower than ±0.5% of the test value or ± 10 mA, whichever is greater,
for phases and ground.
Verify that the relay measures the values with an error lower than ±1.5% of the test value or ± 1 mA, whichever is greater,
for sensitive ground (SG).
GENERAL SETTINGS
NAME
VALUE
UNITS
RANGE
PHASE CT RATIO
1.0
0.1
1.0-6000.0
GROUND CT RATIO
1.0
0.1
1.0-6000.0
STV GROUND CT RATIO
1.0
0.1
1.0-6000.0
PHASE VT RATIO
1.0
0.1
1.0-6000.0
PHASE VT CONNECTION
WYE
N/A
WYE – DELTA
NOMINAL VOLTAGE
100 V
0.1
1-2250 V
NOMINAL FREQUENCY
50 Hz
1 Hz
50-60 Hz
PHASE ROTATION
ABC
N/A
ABC – ACB
FREQUENCY REFERENCE
VI
N/A
VI-VII-VIII
AUXILIARY VOLTAGE
VX
N/A
VX – VN
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
VI
0º
0
5
50
100
150
200
VII
120º
0
5
50
100
150
200
VIII
240º
0
5
50
100
150
200
VX
0º
0
5
50
100
150
200
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Ia (A)
45º
0
15
10
5
1
0.1
Ib (A)
165º
0
15
10
5
1
0.1
Ic (A)
285º
0
15
10
5
1
0.1
IG (A)
0º
0
15
10
5
1
0.1
ISG (A)
0º
0
5
1
0.1
0.01
0.005
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...