![GE Multilin F650 Instruction Manual Download Page 1024](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_5720161024.webp)
I-20
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
I.1 FACTORY DEFAULT SETTINGS
APPENDIX I: FACTORY DEFAULT CONFIGURATION
Pickup Delay for Overcurrent
OC Pickup Delay
0,2
0.01
s
[0.00 : 600.00]
Pickup Level for operating Power
Power Pickup
0,01
0.01
W
[0.01 : 4.50]
Max torque angle
MTA
0
1
Deg
[0 : 360]
Pickup Delay for Operating Power
Power Pickup Delay
0,2
0.01
s
[0.00 : 600.00]
Curve shape
Curve
DEFINITE TIME
N/A [DEFINITE TIME - INVERSE
TIME - USER CURVE A -
USER CURVE B - USER
CURVE C - USER CURVE D]
Multiplier
Multiplier
1
0.01
s
[0.02 : 2.00]
Snapshot event generation
Snapshot Event
DISABLED
N/A [DISABLED-ENABLED]
Setpoint > Control Elements > Setting Group
Setting Description
Name
Default Value
Step Range
User
Value
Setting Grouping Permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A [GROUP 1 – GROUP 2 –
GROUP 3]
Snapshot Event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > Underfrequency
Underfrequency 1 > Underfrequency 2 > Underfrequency 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Pickup level
Pickup Level
49.50
0.01
Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01
s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01
s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
30
1 V
[10 : 300]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Control Elements > Overfrequency
Overfrequency 1 > Overfrequency 2 > Overfrequency 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Pickup level
Pickup Level
50.50
0.01
Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01
s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01
s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
30
1 V
[10 : 300]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...