CHAPTER 9: BOOTCODE AND FIRMWARE UPGRADE
9.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00.
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
9-11
Figure 9-10: IP address setpoint window
These values should match the LAN structure where the relay will be connected.
The relay IP address should have the first three octets corresponding with the gateway and the last octet must be a
free IP address reserved to the relay to avoid possible collisions with other devices.
The gateway must be the one used in the LAN structure connecting the relay
21. After assigning the Ethernet parameters, the upgrade of the boot code is complete and successful.
22. A window is displayed with the message:
Setting Default IP address
, followed by:
Figure 9-11: BOOTware upgrade successful process
After boot code upgrade, the equipment firmware must also be upgraded.
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...