5-20
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
5.2 PRODUCT SETUP
CHAPTER 5: SETPOINTS
Maximum Number of Oscillos (Max. Number Osc.):
1 to 20 oscillography records can be selected.
Automatic Overwrite:
This setting allows chained oscillographies during the fault (TRIGGER OSCILLO signal
activated). The oscillography module is reset once the data has been completely
stored in Flash memory and the TRIGGER OSCILLO state is deactivated.
Snapshot Events:
This setting enables or disables snapshot event generation for the oscillography
element.
Oscillography files calculations
The overall maximum samples capacity is allocated for 27594 samples. The size of each oscillography file depends on the
configured number of oscillographies and is evenly distributed based on the maximum samples value using these
formulas:
Number of samples per oscillography
= (27594 samples)/(Max. Number Osc. setpoint)
Number of cycles per oscillography = (Number of samples per oscillography)/(Samples / Cycle setpoint).
EXAMPLE
For a Max. Number Osc. of 4, each record stores 27594 / 4 = 6898 samples per stored oscillo.
If we set the Samples /Cycle setpoint to 64 samples per cycle, each record stores up to 6898 / 64 = 107.78 signal cycles.
This value expressed in terms of time is:
For 50 Hz: 204.79 cycles x 20 ms/cycle = 4095.8 ms.
For 60 Hz: 204.79 cycles x 16.67 ms/cycle = 3413 ms.
5.2.4.2 Oscillography states
NOTICE
After a change in oscillography settings all oscillography files stored on the flash memory are
erased.
OSCILLOGRAPHY STATES
OSC DIG CHANNEL 1
OSC DIG CHANNEL 2
OSC DIG CHANNEL 3
OSC DIG CHANNEL 4
OSC DIG CHANNEL 5
OSC DIG CHANNEL 6
OSC DIG CHANNEL 7
OSC DIG CHANNEL 8
OSC DIG CHANNEL 9
OSC DIG CHANNEL 10
OSC DIG CHANNEL 11
OSC DIG CHANNEL 12
OSC DIG CHANNEL 13
OSC DIG CHANNEL 14
OSC DIG CHANNEL 15
OSC DIG CHANNEL 16
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...