CHAPTER 5: SETPOINTS
5.4 PROTECTION ELEMENTS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
5-89
The following table shows the SMIN and angle values that must be used for some typical applications:
Table 5-61: Directional power element
By adding 90º to the angles shown on figures a, b, c and d, the represented elements would be similar but with
Reactive
Power
instead of Active Power.
Any other angle would provide a mixed Protection Between Active and Reactive power.
A different angle selection for Stage 1 and Stage 2 can provide in a single element, a Reactive and Active power limitation.
For example, using the following values:
Dir Power Angle 1(RCA)
0º
Stage 1 Tap
0
Dir Power Angle 2(RCA)
90º
Stage 2 Tap
0
We would obtain a mixed Protection Between figure (d) and figure (e).
Settings
Table 5-62: 32 element settings
The snapshot event setting enables or disables the snapshot event generation for this element.
Function:
Enables or disables the directional element.
Blk Time After Close:
In seconds. This settings allow to block the element 32 during the time specified in the
setting after the breaker switches from OPEN to CLOSED.
Dir Power Angle (1-2) (RCA):
This setting specifies the relay characteristic angle (RCA) for the directional power
element. This setting provides ability to respond to the function in any direction
defined (active forward power, active low forward power, etc.)
SMIN (Stage Tap)
ANGLE (RCA)
ELEMENT
>0
0º
Forward Active Power
<0
0º
Reverse Low Forward Active Power
>0
180º
Reverse Forward Active Power
<0
180º
Low Forward Active Power
SETPOINT > PROTECTION ELEMENT > SETTING GROUP X > Power > Directional Power>
Directional Power 1> Directional Power 2 > Directional Power 3
setting Description
Name
Default Value
Step
Range
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Block from offline
Blk Time After Close
0.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 1 (RCA1)
Dir Power Angle 1
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 2 (RCA2)
Dir Power Angle 2
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...