7-196
F650 DIGITAL BAY CONTROLLER
GEK-106310-AF
7.2 IEC 61850 PROFILE FOR F650
CHAPTER 7: IEC 61850 PROTOCOL
8 PIXIT for GOOSE publish model
Description
Value / Clarification
Can the test (Ed1) / simulation (Ed2) flag in the published GOOSE be
set
N
What is the behaviour when the GOOSE publish configuration is
incorrect
DUT keeps GoEna=F.
Configuration tool does not allow wrong
configuration to be uploaded into device. E.g.:
empty dataset.
Published FCD supported common data classes are
SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE,
DEL, SEQ, INC, ENC, SPC, DPC, INC, ENC. (Only
the elements with FC=ST or MX are published).
What is the slow retransmission time
Is it fixed or configurable
Configured by SCL or GoCB MaxTime
What is the fastest retransmission time
Is it fixed or configurable
Fixed. MinTime = 5 ms
Can the GOOSE publish be turned on / off by using
SetGoCBValues(GoEna)
Y
What is the initial GOOSE sqNum after restart
sqNum = 1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
Y
Y (timestamp attributes are not supported)
How is the retransmission curve after a change.
sqNum = 0 New change
sqNum = 1 -> 5ms later with TAL = 1000
sqNum = 2 -> 10ms later with TAL = 1000
sqNum = 3 -> 15ms later with TAL = 4000
sqNum = 4 -> 1000ms later with TAL = Update
time* multipled by 4
sqNum = 5 -> Update time* later with TAL =
Update time* multipled by 4
sqNum = 6-> Update time* later with TAL =
Update time* multipled by 4
sqNum = 7 ……..
………...
………….
*
Update time
is configured in the ICT
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...