I.1 FACTORY DEFAULT SETTINGS
APPENDIX I: FACTORY DEFAULT CONFIGURATION
Setpoint > Protection Elements > Ground Current > Ground Directional >
Ground Directional 1 > Ground Directional 2 > Ground Directional 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Maximum Torque Angle
MTA
-45
1
Deg [-90 : +90]
Operation Direction
Direction
FORWARD
N/A [FORWARD – REVERSE]
Polarization type
Polarization
VO
N/A [V
0
– I
P
– V
0
+I
P
– V
0
*I
P
]
Block logic type
Block Logic
PERMISSION
N/A [BLOCK – PERMISSION]
Polarization voltage threshold
Pol V Threshold
10
1 V
[0 : 300]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Sensitive Ground Current > Sensitive Ground TOC
Sensitive Ground TOC 1 > Sensitive Ground TOC 2 > Sensitive Ground TOC 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A [PHASOR – RMS]
Pickup level
Pickup Level
0.050
0.00
1 A
[0.005 : 16.000]
Curve shape
Curve
IEEE Ext Inv
N/A [See list of curves]
Time Dial
TD Multiplier
1.00
0.01
s
[0.00 : 900.00]
Reset type
Reset
INSTANTANEOUS
N/A [INSTANTANEOUS – LINEAR]
Snapshot Event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Sensitive Ground Current > Sensitive Ground IOC
Sensitive Ground IOC 1 > Sensitive Ground IOC 2 > Sensitive Ground IOC 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A [PHASOR – RMS]
Pickup level
Pickup Level
0.100
0.00
1 A
[0.005 : 16.000]
Trip time
Trip Delay
0.00
0.01
s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01
s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Sensitive Ground Current > Isolated Ground IOC
Isolated Ground IOC 1 > Isolated Ground IOC 2 > Isolated Ground IOC 3
Setting Description
Name
Default Value
Step Range
User
Value
Function Permission
Function
DISABLED
N/A [DISABLED – ENABLED]
High Voltage level
Vh Level
20
1 V
[2 : 70]
Low Current level
Il LEVEL
0.005
0.00
1 A
[0.005 : 0.400]
Low Voltage level
Vl LEVEL
2
1 V
[2 : 70]
High Current level
Ih LEVEL
0.025
0.00
1 A
[0.005 : 0.400]
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...