CHAPTER 9: BOOTCODE AND FIRMWARE UPGRADE
9.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00.
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
9-9
16. It is important to switch the Relay OFF and ON again during the time shown by the progress bar; in case this time
expires, the program offers the option to continue with the process or to postpone, verify the correct RS232
connections and try again later. Notice that the serial COM PORT used in the boot upgrade procedure is the one
selected in step 4 above.
Figure 9-9: loading update file error message
If the relay gets stuck during the upgrading process after switching OFF and ON the relay, giving error message shown, it
is due to no serial communication via the front RS232 port. Check the serial cable and serial settings connection. At this
point the relay will not be upgraded.
After switching it OFF and ON it will continue working with the former firmware and bootware versions.
17. After switching the relay OFF and ON, if the serial communication between EnerVista 650 Setup and the relay is
correct the program shows the following message:
Then it requires the confirmation to proceed to upgrade:
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...