APPENDIX I: FACTORY DEFAULT CONFIGURATION
I.1 FACTORY DEFAULT SETTINGS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
i-19
Curve shape
Curve
DEFINITE TIME
N/A [DEFINITE TIME – INVERSE
TIME]
Time Dial
Delay
10.00
0.01
s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Power > Forward Power
Forward Power 1 > Forward Power 2 > Forward Power 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Block from offline
Blk Time After Close
0.00
0.01
s
[0.00 : 900.00]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01
MW [0.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01
s
[0.00 : 900.00]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01
MW [0.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01
s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Power > Directional Power>
Directional Power 1 > Directional Power 2 > Directional Power 3
Setting Description
Name
Default Value
Step Range
User
Value
Function permission
Function
DISABLED
N/A [DISABLED – ENABLED]
Block from offline
Blk Time After Close
0.00
0.01
s
[0.00 : 900.00]
Directional Angle for stage 1
Dir Power Angle 1
0.00
0.01
Deg [0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01
MW [-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01
s
[0.00 : 900.00]
Directional Angle for stage 2
Dir Power Angle 2
0.00
1
Deg [0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01
MW [-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01
s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Power
WATT GND FLT HIGH 1 > WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1 > WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A [DISABLED-ENABLED]
Supervision minimum voltage
Voltage Pickup Level
2
0.01
V
[2.00 : 70.00]
Source of operating current.
Current selection
IN
N/A [IN-IG]
Pickup Level for Overcurrent
OC Pickup Level
0,005
0.00
1A
[0.005 : 0.400]
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...